三、型号、名称Type and Designation
型号Type | 名称Designation |
YJV YJLV |
铜芯或铝芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation and PVC sheath |
YJY YJLY |
铜芯或铝芯交联聚乙烯绝缘聚乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation and PE sheath |
YJV22YJLV22 |
铜芯或铝芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,steel tape armor and PVC sheath |
YJV23YJLV23 |
铜芯或铝芯交联聚乙烯绝缘钢带铠装聚乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,steel tape armor and PE sheath |
YJV32YJLV32 |
铜芯或铝芯交联聚乙烯绝缘细钢丝铠装聚氯乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,thin steel wire armor and PVC sheath |
YJV33YJLV33 |
铜芯或铝芯交联聚乙烯绝缘细钢丝铠装聚乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,thin steel wire armor and PE sheath |
YJV42YJLV42 |
铜芯或铝芯交联聚乙烯绝缘粗钢丝铠装聚氯乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,thin steel wire armor and PVC sheath |
YJV43YJLV43 |
铜芯或铝芯交联聚乙烯绝缘粗钢丝铠装聚乙烯护套电力电缆 Power cable with Cu/AI conduetor, XLPE insulation,thin steel wire armor and PE sheath |
ZR-YJV ZR-YJLV |
铜芯或铝芯交联聚乙烯绝缘聚氯乙烯护套阻燃电力电缆 Flame-retardant power cable with Cu/AI conduetor, XLPE insulation and PVC sheath |
ZR-YJV22ZR-YJLV22 |
铜芯或铝芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套阻燃电力电缆 Flame-retardant power cable with Cu/AI conductor, XLPE insulation, steel tape armor and PVC sheath |
ZR-YJV32ZR-YJLV32 |
铜芯或铝芯交联聚乙烯绝缘细钢丝铠装聚氯乙烯护套阻燃电力电缆 Flame-retardant power cable with Cu/AI conductor, XLPE insulation, thin steel wire armor and PVC sheathsheath |
ZR-YJV42ZR-YJLV42 |
铜芯或铝芯交联聚乙烯绝缘粗钢丝铠装聚氯乙烯护套阻燃电力电缆 Flame-retardant power cable with Cu/AI conductor, XLPE insulation, thin steel wire armor and PVC sheathsheath |
NH-YJV NH-YJLV |
铜芯或铝芯交联聚乙烯绝缘聚氯乙烯护套耐火电力电缆 Flame-retardant power cable with Cu/AI conductor. XLPE insulation and PVC sheath |
NH-YJV22NH-YJLV22 |
铜芯或铝芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套耐火电力电缆 Flame-retardant power cable with Cu/AI conductor. XLPE insulation and PVC sheath |
NH-YJV32NH-YJLV32 |
铜芯或铝芯交联聚乙烯绝缘细钢丝铠装聚氯乙烯护套耐火电力电缆 Flame-retardant power cable with Cu/AI conductor. XLPE insulation and PVC sheath |
NH-YJV42NH-YJLV42 |
铜芯或铝芯交联聚乙烯绝缘粗钢丝铠装聚氯乙烯护套耐火电力电缆 Flame-retardant power cable with Cu/AI conductor. XLPE insulation and PVC sheath |
耐火电缆YJV 5 6平方高温芯电力电缆YJV 5 * 6 GB阻燃线
名称:耐火电线电缆
分类:阻燃电缆规格
GB:GB / T19666-2005
模型
额定电压
核心数
部分
ZA(B,C)N-VV,YJV
ZA(B,C)N-VV22,YJV22
ZA(B,C)N-VV23,YJV23
0.6 / 1kv
1,2,3,4,5,3 + 1,3 + 2,4 + 1
1.5-800
ZA(B,C)N-KVV
ZA(B,C)N-KVV22
450 / 750v
2?61
1.5-10
ZA(B,C)N-BV
450 / 750v
1个
1.5-400
ZA(B,C)N-BVV
300 / 500v
2?5
1.5-35
1.交流额定电压:U。/ U(V系列:600 / 1000V,K系列:450 / 750V,B系列:450 / 750V)。
2.电缆高长期温度
(1)绝缘和护套的阻挡层PVF:70 CEL和105 CEL两种; XLPE绝缘:90 CEL;
(2)氟塑料绝缘和护套:220 CEL和260 CEL两种;氟塑料绝缘和105 CEL阻燃聚氟乙烯护套:90 CEL和125 CEL两种。
(3)低卤素阻燃聚氯乙烯绝缘和护套:70 CEL;无卤阻燃聚烯烃绝缘和护套:90 CEL和125 CEL两种。
交联聚乙烯绝缘电力电缆
XLPE insulated power cable
1115610781一、执行标准Application
本产品按GB/T12706-2008生产,阻燃耐火电缆按照GB/19666-2005、GB/T12706-2008设计。
二、用途Application
本产品适用于35kV及以下电力输配电系统中、供输配电能之用。广泛应用于电力、建筑、工矿、冶金、石油化共、交通等部门,已完全代替了油浸纸绝缘电力电缆和部分替代了聚氯乙烯绝缘电力电缆。
It is used to transmit and distribute power in power trans mission and dis tribution system of 35kV or lower, Ith is generallyu applied to the fields
including power , construction, mines, metallurgy, petrochemical indstry and communication in complete replaceof oilimmersed paper in sulated power
cable and in partial replace of PVC in sulated power cable.
4.有关类型和名称,请参见表1
类型
名称
铜导体
铝导体
合资公司
N-YJLV
交联聚乙烯绝缘聚氯乙烯护套阻燃电力电缆
ZA(BC)N-YJV
ZA(BC)N-YJLV
交联聚乙烯绝缘聚氯乙烯护套阻燃耐火电力电缆
N-YJV22
N-YJLV22
交联聚乙烯绝缘钢带铠装聚氯乙烯护套耐火电力电缆
ZA(BC)N-YJV22
ZA(BC)N-YJLV22
交联聚乙烯绝缘钢带铠装聚氯乙烯护套阻燃耐火电力电缆
5.结构形式
5.1导体/防火绝缘层/普通绝缘层/电缆/填料/捆扎/护套
5.2导体/防火绝缘层/普通绝缘层/电缆/绑扎/垫层/铠装/护套
6.电缆规格见表2:
类型
核心数
主磁芯的标称横截面积mm2
铜导体
铝导体
N-YJV ZA(B.C)N-YJV
-
N-YJV22 ZA(BC)N-YJV22
-
N-YJLV ZA(B.C)
N-YJLV22 ZA(BC)N-YJLV22
1个
1.5-240
2.5-240
10-240
N-YJV ZA(B.C)
-
N-YJV22 ZA(BC)N-YJV22
-
N-YJLV ZA(B.C)
N-YJLV22 ZA(BC)N-YJLV22
2
1.5-240
2.5-240
4-240
N-YJV ZA(B.C)
-
N-YJV22 ZA(BC)N-YJV22
-
N-YJLV ZA(B.C)N-YJLV
N-YJLV22 ZA(BC)N-YJLV22
3
1.5-240
2.5-240
4-240
N-YJV ZA(B.C)
-
N-YJV22 ZA(BC)N-YJV22
-
N-YJLV ZA(B.C)
N-YJLV22 ZA(BC)N-YJLV22
3 + 1
1.5-240
2.5-240
4-240
N-YJV ZA(B.C)
N-YJV22 ZA(BC)N-YJV22
N-YJLV ZA(B.C)N-YJLV
N-YJLV22 ZA(BC)N-YJLV22
4
4-185
4-185
N-YJV ZA(B.C)
N-YJV22 ZA(BC)N-YJV22
N-YJLV ZA(B.C)
N-YJLV22 ZA(BC)N-YJLV22
4 + 1
2.5-240
2.5-240
N-YJV ZA(B.C)
N-YJV22 ZA(BC)N-YJV22
N-YJLV ZA(B.C)N-YJLV
N-YJLV22 ZA(BC)N-YJLV22
3 + 2
2.5-240
2.5-240
N-YJV ZA(B.C)
N-YJV22 ZA(BC)N-YJV22
N-YJLV ZA(B.C)N-YJLV
N-YJLV22 ZA(BC)N-YJLV22
5
2.5-25
2.5-25
7.主要技术要求
防火性能必须符合表3的规定
表3防火性能要求
码
适用范围
加热时间加冷却时间(分钟)
测试电压V
验收标准
测试方法
?
0.6 / 1KV以下电缆
90 + 15
额定电压
1)2A保险丝没有损坏
2)指示灯不熄灭
GB / T19216.21
注意:加热温度在750到800℃之间
成束电缆的阻燃性能必须符合表4的规定
表4束状电缆阻燃性能要求
码
样品体积(非金属材料)L / M
加热时间
验收标准
测试方法
ZA
7
40
焦高≤2.5m
GB / T18380.3
ZB
3.5
40
零碳
1.5
20
产品其他性能应符合表5的规定
表5
标称横截面积mm2
标称厚度
毫米
绝缘线芯
火花测试kv
交流电压测试
导体直流电阻(20℃以下)
不得超过Ω/ km
铜导体
铝导体
1.5
0.8
5
3.5
12.1
-
2.5
0.8
5
3.5
7.41
-
4
1.0
6
3.5
4.61
7.41
6
1.0
6
3.5
3.08
4.61
10
1.0
6
3.5
1.83
3.08
16
1.0
7
3.5
1.15
1.91
25
1.2
7
3.5
0.727
1.20
35
1.2
8
3.5
0.524
0.868
50
1.4
9
3.5
0.387
0.641
70
1.4
9
3.5
0.268
0.443
95
1.6
9
3.5
0.193
0.32
120
1.6
9
3.5
0.153
0.253
150
1.8
9
3.5
0.124
0.206
185
2.0
9
3.5
0.091
0.164
240
2.2
9
3.5
0.0754
0.125